Cabinet installation standards
|
Can be installed in a standard 19" 800 mm-deep cabinet. A H w 2.2 m-high N68E cabinet is used by default.
|
|
Dimensions without packaging (H x W x D) [mm(in.)]
|
930 mm x 442 mm x 650 mm (36.61 in. x 17.40 in. x 25.59 in.) (Chassis main body)
930 mm x 442 mm x 750 mm (36.61 in. x 17.40 in. x 29.53 in.) (Dimensions of the chassis body together with cable trays and front and back attachments)
|
|
Chassis height [U]
|
21 U
|
|
Weight without packaging (base configuration) [kg(lb)]
|
78.9 kg (173.94 lb)
|
|
Weight without packaging (full configuration) [kg(lb)]
|
[400G bundle] 186.1 kg (410.28 lb)
[1T bundle] 209 kg (460.77 lb)
|
|
Typical power consumption [W]
|
4110 W (fully configured with BSUF-240s)
4770 W (fully configured with BSUF-480s)
6520 W (fully configured with BSUF-1Ts)
|
|
Typical heat dissipation [BTU/hour]
|
13334.6 BTU/hour (fully configured with BSUF-240s)
15475.9 BTU/hour (fully configured with BSUF-480s)
21153.6 BTU/hour (fully configured with BSUF-1Ts)
|
|
MTBF [year]
|
year36.23
|
|
MTTR [hour]
|
hour0.5
|
|
Availability
|
0.999998425
|
|
Power supply mode
|
DC built-in
|
|
Maximum number of power chassis inputs
|
(8 channels/PEM)*2 PEM=(2 channels/PM)*4 PM*2 PEM=16 channels
|
|
Rated input voltage [V]
|
–48 V/ –60 V
|
|
Input voltage range [V]
|
–40 V to –72 V
|
|
Maximum input current [A]
|
63 A/single-module
|
|
Maximum input cable diameter [mm²]
|
35 mm²/channel
|
|
Front-end circuit breaker/fuse [A]
|
2 channels of 63 A/single-module
[400G bundle] DC device: 4 PMs, with a total of 8 channels of 63 A
[1T bundle] DC device: 6 PMs, with a total of 12 channels of 63 A
|
|
Noise at normal temperature (acoustic power) [dB(A)]
|
NEBS-compliance (
< 78 dBA @ 27°C (80.6°F)) |
|
Number of slots
|
12
|
|
Number of service board slots
|
8 |
|
Switching capacity
|
25.16 Tbps (BSUF-1T)
|
|
Redundant MPUs
|
1:1
|
|
Redundant Switch fabrics
|
3+1
|
|
Redundant power supply
|
[400G bundle] 3+1
[1T bundle] 5+1
|
|
Redundant fans
|
[400G bundle] 2 assemblies in support for proper fan operation in case of a single fan failure for a short period at 40°C (104°F)
[1T bundle] 3 assemblies in support for proper fan operation in case of a single fan failure for a short period at 40°C (104°F)
|
|
Long-term operating temperature [°C(°F)]
|
0°C to 45°C (32°F to 113°F)
|
|
Short-term operating temperature [°C(°F)]
|
-5°C to 55°C (23°F to 131°F)
|
|
Restriction on the operating temperature variation rate [°C(°F)]
|
≤ 30°C/hour (86°F/hour)
|
|
Storage temperature [°C(°F)]
|
-40°C to 70°C (-40°F to 158°F)
|
|
Long-term operating relative humidity [RH]
|
5% RH to 85% RH, non-condensing
|
|
Short-term operating relative humidity [RH]
|
5% RH to 95% RH, non-condensing
|
|
Storage relative humidity [RH]
|
5% RH to 95% RH, non-condensing
|
|
Long-term operating altitude [m(ft.)]
|
≤ 4000 m (13123.2 ft.) (For the altitude in the range of 1800 m to 4000 m [5905.44 ft. to 13123.2 ft.], the operating temperature of the device must decrease by 1°C [1.8°F] for every 220 m [721.78 ft.].)
|
|
Storage altitude [m(ft.)]
|
Less than 5000 m (16404 ft.)
|